19
Instructionsforuseofthemachine–sectionkinthismanual
Instructionsaboutadjustmentandmaintenance–sectionrinthismanual
Safetyduringadjustmentandmaintenance–sections
f.Employeesinchargeofoperation/control/maintenance
Afterstart‐upandhand‐overfrominstallertooperators,theunitoperatesfullyautomatically.
IndicationsofoperatingstatusaswellasindicationoffaultsarevisibleinadisplayandonLEDsatahand
terminal.Theoperatorscanenternewparametersinacontrollerviabuttonsonahand
terminal.
Alternatively,thecontrollercanbeconnectedtoaBMSsystemsothatnewparameterscanbeselectedvia
PC,tabletorSmartphone.Theoperatorsdonotneedtoopeninspectionsdoorsfortheoperatio n
Skilledtechniciansmustcarryoutmaintenanceaswellasrepairs.
g.Intendeduseandrangeofapplications
Theairhandlingunitsareintendedforthetransportandtreatmentofairbetween‐40°Cand+40°C
Theunitsareexclusivelyforcomfortventilation.Theunitsarenotforenvironmentsthatexceedthe
corrosionclassC4accordingtoENISO12944‐2.
Intendedapplicationsfortheunitsare:
Offices,teachingrooms,hotels,shops,homesandsimilarcomfortzones.
h.Unintendeduseandmisuse–inappropriateapplicationsforthe
machine
Unitsforoutdoorinstallationmustbespecifiedandorderedforoutdoorinstallation.
TheunitsmustnotbeusedinenvironmentsthatexceedcorrosionclassC4accordingtoENISO12944‐2,
andfortransportofsolidparticles.
Examplesofnotintendeduse:
Kitchenextraction,swimmingpools,off‐shore,Ex‐areas,drying
ofwashedclothes.
Donotusetheunitwithpartlyfinishedductsystems.Donotusetheunitforventilationofthebuildingsite
untiltheunitisproperlyprovidedwithguards.
h.1Airhandlingunitinoperation
Thepressuredifferencebetweeninteriorandexterioroftheunitmustnotexceed2000PafortheDV10
anduptoDV150(includingDV150),and1500PaforDV190andDV240.
Beforestart‐upoftheunitallducts,safetyguardsandallprotectivedevicesmust
bemountedtoprevent
anyaccesstorotatingfanimpellers.Allinspectiondoorsmustbeclosedandlockedwhentheunitisin
operation.
Donotusetheunitwithoutfilters.
