SystemAir DANVENT DV10 - Instructions Designed to Enable Adjustment and Maintenance to be Carried out Safely, Including the Protective Measures that Should be Taken During These Operations; S.1. Protective Measures and Additional Protective Measures; S.1.1 Necessary Protection Measures Prior to Start-Up; S.1.1.1 Design of Protection Measures

SystemAir DANVENT DV10
120 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
54
s.Instructionsdesignedtoenableadjustmentandmaintenancetobe
carriedoutsafely,includingtheprotectivemeasuresthatshouldbetaken
duringtheseoperations
s.1.Protectivemeasuresandadditionalprotectivemeasures
Adjustmentandmaintenancemustbedonebyskilledtechnicians–usuallybasedonservicecontractsfor
someyearsorlong‐termESCOcontracts.
Theunitsareprovidedwithguardstoavoidunintendedhazardsandinjurybecauseofrotatingpartsinthe
unit.Thepotentialsourcesofharmarethefanswith
fastrotatingimpellers.Hazardsfromtheimpellers
areobviousduringoperation,butwhenpoweriscut‐off,theimpellersarestillpotentialhazardsdueto
after‐runforatleast20seconds.Noticethatevencut‐offtheimpellersarestillpotentialhazards.
Thefanguard’saretheinspectiondoors
andthedoorsareprovidedwithlocks.Insidethedoorsare
additionalprotectioninstalled–guardsthatonlycanberemovedbyuseoftools.
Othermotor‐drivenpartsaredamperswithdampermotorsandrotaryheatexchangers,butthemovement
issoslowthatguardmeasuresarenotnecessary.Just
keepyourhandsawayfromplaceswithriskofinjury.
Useparticulaterespiratorwhenfiltersarereplaced.
s.1.1Necessaryprotectionmeasurespriortostart‐up.
Ensurethatallprotectionmeasuresareinstalledcorrectbeforestart‐up.
s.1.1.1Designofprotectionmeasures
Insidethedoorsareadditionalprotectioninstalled–guards
thatonlycanberemovedbyuseoftools.
s.1.1.2Configurationoffrequencyconverters withinstalledguard
Afrequencyconverterismountedbesidethefaninsomeunits.Iftheconfigurationoffrequencyiscarried
outwiththefaninoperation,theguardmustbeinstalledforsafetyreasonsanda
longcablemustbe
installedbetweenthefrequencyconverterinsidetheunitandthecontrolpaneloutsidetheunit.
s.1.2Safeadjustmentandmaintenance
Beforemaintenanceandrepair,theunitmustbeswitchedoffbyswitchingofftheautomaticcircuit
breakersandblockthembypadlocks..Seetheillustrationbelow
abouthowtoplaceapadlockoneach
automaticcircuitbreaker.Notethatlampsmustbeswitchedonduringmaintenance(lampsarean
accessory–onlyinstalled,ifordered).
Usecut‐resistantglovesforprotectionagainstinjuryfromsharpmetalplateedges.UseCE‐markedgloves
forthispurpose.Use
helmetduringmaintenanceworkintheunit.

