39
l.9HeatpumpunitstypeDVU
l.9.1Riskofhightemperature
Hazards/dangerousarea:
Condenserbatteriesandpipescanachievetemperatureof60degreeCelsius.
Dangerousincident:
VurderetudfraISO137321:2006,dererumiddelbartikkerisikoforforbrændinger.(berøringstid2,5sek).
Claimforreductionofdanger:
No.
l.9.2Riskcausedbylightningstrike
Hazards/dangerousarea:
Lightningstrikeclosetothemachine.
Dangerousincident:
Lightningstrikecancreateflashoverbetweenphasesandconductiveparts.Thiscancausefireorthe
overvoltagecanmakeinjuryonpersons.
Claimforreductionofdanger:
Installerandusermustbeawareofthefactthatlightningmakesariskthatrequiresinstallationof
overvoltageprotectiondevicestoleadthelightningovervoltagetoanearthleadonasafeway.Theneed
forovervoltageprotectiondevicesdependonwheretheunitisplacedinandonthe
building.
Installerandusermusttakecareofthisaccordingtolocalstatutoryrequirements.Overvoltageprotection
devicesarealsodescribedinsectioni.3.1ofthismanual.
m.Instructionsontheprotectivemeasurestobetakenbyallservice
techniciansduringrepairandmaintenance
Usethebelowmentionedpersonalprotectiveequipmentformaintenance:
Cutresistantglovesforprotectionagainstinjuryfromsharpmetalplateedges.UseCEmarked
glovesforthispurpose.
Helmet
Particulaterespiratormaintenancefreeincludingfoamfacesealandadjustableprethreaded
headbandsforreplacingfilters.
Padlockforlockingtheautomaticcircuitbreakersinoffposition
Permanentmagnetmotor.Theshaftmustbeblockedduringrepairsandmaintenanceofthe
electricsystem(themotorgenerateselectricitybyrotationforexamplethatthewindand
thermicdrivesthefan/motor).
Lightinginsidetheunits.According
tothelatestinterpretationsoftheMachineryDirectivebythe
authoritiessufficientlightinginsidetheunitsismandatory.
Toolstoblocktheimpellerduringrepairsandmaintenanceifstackeffectalsocalledchimney
effectintheductscreateairflowsthatdrivestheimpellersbyturnedoffmotors
n.Theessentialcharacteristicsoftoolswhichmaybefittedtothe
machinery
ThesubjectintheMachineryDirectiveabouttoolsonthemachinedoesnotexistfortheDVairhandling
units,becausethosetoolsdoesnotexist.
