12—4
12.3AC‐fanoperationwithoutthermistorforDanfossFC101
Systemairfactoryset‐upisbasedonDanfossinitialization.
14‐22:Operationmode: [2]Initialisation(DanfossInitialisation)
Turnpoweroffandon.
Systemairfactoryset‐up:
0‐01:Languageselection:
1‐03:Torquecharacteristic:
 [3]Auto‐Energyoptim.
1‐20:Motorpower: Accordingtomotorplate
1‐24:MotorCurrent: Accordingtomotorplate
1‐25:MotorNominalSpeed: Accordingtomotorplate
1‐29:Automaticmotoradption(AMA): [1]Kompl.motoradaptionto(Turnpoweroffandon.)
1‐42:MotorCableLength:
Orderspecific
1‐50:
MotorMagnetisationatzerospeed.: 0 %
1‐52:
Min.SpeedNormalMagnetisation: 10Hz
1‐73:Flyingstart:  [1]Enable
5‐40.0:FunctionRelay: [3]Driveready/remote
14‐03:Overmodulation: [1]Active
14‐20:ResetMode: [2]Automaticresetx2
0‐50:LCPCopy: [1]AlltoLCP(CopyofSystemairfactorysettingstopanel)