31

i.4.4.3.2Pipeconnectiontocoolingcoilsforchilledwater
Coilswith3rowsormoremustalwaysbeconnectedincounterflowtotheairflow.
NOTE:Theglycolmustbewithoutadditivesandautoglycolmustnotbeused.
Automaticbleedinghastobeinstalledatthe
highestpointofthe2pipessupplyorreturnpipe.

Toprotectagainstfrostatemperature
sensorforthetransmissionofananalog
signaltothecontrollerisplacedina
pipeonthecollectionpipeforreturn
water.Thesensormustbefittedwater
tightwithacapinthepipebeforewater
underpressureisinthebattery.The
pipeforthesensorissolderedonthe
collectionpipeanditisimportantto
holdcontraonthepipe,whenthecapis
tightened.
Batteryseenfromabove.Thesensor
measuresthewatertemperatureofthe
waterinsideoneofthesmallpipesfor
returnwaterinthebattery.Thesensor
reducestheareainthispipeandhereby
alsotheflowofwarmwaterinthispipe.
Thetemperatureinthispipeisreduced
morethanthetemperatureinallother
pipesbytheairflowthroughthe
battery.Becausethelowest
temperatureinthebatteryprobablyis
measuredhere,thissystemcreates
earlyandsafewarningoffrost.
Itisimportantthatthecapistightened
sufficienttokeepthesensorsystem
fullywatertight.