9-5
| Speed control for rotor and assembly of divided rotor
By delivery of a Geniox — C module with divided rotor,
the motor is installed before delivery to the customer
The drive belt must be placed around the rotor and the
ideal distance is 9 cm from the 2 sides of the rotor. The
rotors are always 20 cm thick. The distance to the drive
belt from a side of the rotor must be between 9–11 cm.
the 2 sides of the rotor.
Motor is mounted on the motor console plate and 4 shock
absorbers are mounted under the plate with M8 bolts.
Sensor for control of rotation must be installed by the
installer. Distance must be 1-4 mm between sensor and
rotor. Check that the brackets which are used for the
assembly of the rotor segments do not hit the sensor.
Pay attention to the heights of the brackets which are
used for the assembly of the rotor segments. Please turn
the rotor by hand in order to verify that the sensor will
not be hit by the brackets.