9.Scroll up to parameter 20-21 Setpoint 1 and
press OK.
10.Set the system’s flow at design point (flow value
that was specified at the time of order is already
displayed) and press [OK].
a.Parameter 20-21 Setpoint 1.
11.Press the [Auto on] button.
12.Press the [Status] button to get back to the main
screen.
a.Let the drive ramp up to the design flow point
that was specified.
b.IMPORTANT: Allow the pump enough time to
settle out at the specified design flow.
c. IMPORTANT: Record the Hz and ft WG dis-
played on the top of the LCD.
13.Press the [Off] Button.
a.Wait for the pump to come to a complete stop
before moving to the next step.
12.3.2 Set Adjusted Operating Point at
Design Flow
Figure 12-5: Set Control Curve Max (Point C)
Point C
1.Press the [Quick Menus] button.
2.Press the [OK] button to enter “My Personal
Menu.”
3.Scroll down to parameter 0-10 Active Set-up
and press OK.
4.Change Active Set-up from “Set-up 3” to “Set-up 1”
then press OK.
a.Parameter 0-10 Active Set-up.
b.You will know the change has happened when
you see change to .
Before
After