Taco® SKV
43
302-365, Effective: June 5, 2017
© 2017 Taco, Inc.
5.Scroll down to parameter 20-00 Feedback
Source and press OK.
6.Change feedback from “Sensorless Pressure” to
“No function” then press OK.
a.Parameter 20-00 = Feedback 1 Source.
7.Scroll down to parameter 1-00 Configuration
Mode and press OK.
8.Change the Configuration Mode from “Closed
Loop” to “Open Loop” then press OK.
a.Parameter 1-00 = Configuration Mode.
9.Scroll down to to parameter 22-86 Speed at
Design Point and press OK.
10.Enter the Hz you recorded in Set-up 3 (from Step
12 above) and press OK.
a.Parameter 22-86 = Speed at Design Point [Hz].
11.Scroll down to parameter 20-00 Feedback
1 Source and press OK.
12.Change feedback from “No function” to “Sensor-
less Pressure” and press OK.
a.Parameter 20-00 = Feedback 1 Source.
13.Scroll down to parameter 1-00 Configura-
tion Mode and press OK.
Before
After
Before
After
Before
After

Table of Contents