a.Parameter 20-21 Setpoint 1.
8.Press the [Auto on] button.
9.Press the [Status] button to get back to the main
screen.
a.Let the drive ramp up to the design flow point
that was specified.
b.IMPORTANT: Allow the pump enough time to
settle out at the specified design flow.
10.Press the [Off] Button.
a.Wait for the pump to come to a complete stop
before moving to the next step.
11.Press the [Quick Menus] button.
12.Press the [OK] button to enter “My Personal
Menu.”
13.Scroll down to parameter 0-10 Active Set-
up and press OK.
14.Change Active Set-up from “Set-up 3” to “Set-up
1” then press OK.
a.Parameter 0-10 Active Set-up.
b.You will know the change has happened when
you see change to .
15.Scroll down to parameter 20-00 Feedback
Source and press OK.
16.Change feedback from “Sensorless Pressure” to
“No function” then press OK.
a.Parameter 20-00 = Feedback 1 Source.
17.Scroll down to parameter 1-00 Configura-
tion Mode and press OK.
18.Change the Configuration Mode from “Closed
Loop” to “Open Loop” then press OK.