Taco® SKV
71 302-365, Effective: June 5, 2017
© 2017 Taco, Inc.
• manual reset alarm [3]
Dry-Run Settings
1.Press [Main Menu].
2.Scroll down to parameter 22-** Appl. Func-
tions.
3.
Press [OK].
4.Scroll Down to parameter 22-2* No-Flow
Detection.
5.Press [OK].
6.Scroll down to parameter 22-26 Dry Pump
Function.
Press [OK].
7.Change parameter 22-26 to desired feature.
8.Press [Back].
9.Scroll down to parameter 22-27 Dry Pump
Delay.
10.Select the amount of time the pump will run after
dry-run is detected, before going into the mode
selected in Parameter 22-26.
14.1.3 End-Of-Curve
Definition: End-of-curve = pump yielding too large a vol-
ume to ensure the set pressure @ 60Hz max speed con-
dition).
Pump response options:
• off [0],
• warning + run [1] (Factory default mode for SelfSens-
ing pump)
• alarm + trip [2]
• manual reset alarm [3]
End-Of-Curve Settings
1.Press [Main Menu].
2.Scroll down to parameter 22-** Appl. Func-
tions.
3.Press [OK].