4.Scroll Down to parameter 22-5* End of
Curve.
5.Press [OK].
6.Press [OK] to change parameter 25-50 End
of Curve Function.
7.Change parameter 22-50 to desired feature.
8.Press [Back].
9.Scroll down to parameter 25-51 End of Curve
Delay.
10.Select the amount of time the pump will run after
end-of-curve is detected, before going into the
mode selected in Parameter 25-50.
14.1.4 Function at Inverter Overload
Definition: Function at Inverter overload = running along
HP limit curve.
Pump response options:
default VFD trips at 110% rated current [0];
de-rate VFD when load exceeds rating via speed
reduction [1]. (Factory default mode for SelfSensing
pump)
Function at Inverter Overload Settings
1.Press [Main Menu].
2.Scroll Down to parameter 14-** Special
Functions.
3.Press [OK].
4.Scroll Down to parameter 14-6* Auto Derate.
5.Scroll down to parameter 14-61 Function at
Inverter Overload.
6.Press [OK].
7.Change parameter 14-61 to desired feature.