FY operation manual 38
10.13 Fast Level All Parameters Display
FY/FA controller provides a fast parameter access operation, easy for users to quickly access communication group, program group,
motor valve group related parameters
Enter fast level : press down key for 3 seconds at any level
Leave fast level : press down key for 3 seconds at fast level
Any Level
Press key
3 seconds
OPFT
Motor valve traveling time
RUCY
INP1
Input type selection
CYT1
Motor valve action interval time
HYS1
Motor valve action sub
adjustment
HYSM
Motor valve action main
adjustment
RH.TM
MLNB
PSL
BITS
Protocol selection
Data format
BAUD
IDNO
Baud rate
Controller station
W_MD
EEPROM protection
W_MD
PV2
remote function or motor valve
feedback value
MOLH
Main output zero calibration
MOLL
Main output span calibration
OPFT
Output filter
RH.TC
RH.PO
RH.TM
Dehumidification temperature
Dehumidification manipulated value
dehumidification time
PMAC
Automatic valve position
adjustment
INP1
HBOP
Output percentage of trigger HBA
MLNB
Piece linear compensation
segment select
COMP
Piece linear compare value
OFFS
Piece linear offset value
TRCL
Main input TC/RTD zero
calibration
TRCH
Main input TC/RTD span
calibration
TP_K
reserve
PVOH
PV bias(for span)
10.14 Fast Level Parameter
Main input type selection
Change this parameter USPL&LSPL
will be reset
(please refer to Chapter 4 Input Range
Table)
Motor valve traveling time
Time unit
:
second
(Please refer to Chapter 11.6)
Motor valve action interval time.
Time unit : second
Motor valve action main adjustment
unit : percentage
Motor valve action sub adjustment
unit : percentage
Automatic valve position adjustment
0 : OFF stop automatic adjust
1 : ON start automatic adjust
2 : E_PB Valve position determined
by external button