DC Inverter Air
2. If it is normal, please test whether the resistance of exhaust temperature sensor is
consistent with that in attached page (Annex 3);
3. If it is normal, please replace the main control panel.
P34: Driver Radiator Temperature Protection of Outdoor
Unit Treatment Method:
1. Test whether the driver radiator temperature is normal (below 80°);
2. If it is normal, please test whether the resistance of driver radiator temperature is
consistent with that in attached page (Annex 3);
3. If it is normal, please replace the main control panel.
18K ,24K Outdoor unit fault handling
Outdoor board running status indicator light
1、The main controller LED lamp is located in the center position of the outdoor PCB and set the running status
indicator light (yellow luminous tube). When the air conditioner is no fault and the compressor doesn’t running
the indicator light flash at 1 second frequency. The outdoor light always lit when the compressor runs normally;
If there is a fault, the indicator light will flash at 1 second frequency for n times and then destroy 3 seconds for a
cycle to show the fault, as follows:
Input voltage lower than 160V±5V
Running current exceeds a limited value (no displayed)
Exhaust temperature exceeds shutdown protection value
The temperature of the indoor tube is lower than the set value
The temperature of the indoor tube is higher than the set value
The temperature of the indoor tube is higher than the set value
Cooling when outdoor below 0℃ or heating when outdoor higher
protection of outdoor unit
Compressor driven is abnormal or can't be started
Temperature and current of variable frequency module are
Communication abnormal between outdoor PCB power board and
No Communication between indoor and outdoor or outdoor power
The temperature of the indoor tube is lower than the set value
98/ 113