DC Inverter Air
Evaporator tube
E2
26
The temperature of the indoor tube is higher than the set value
temperature sensor
when cooling mode.
Condenser tube
E3
10
The temperature of the indoor tube is higher than the set value
temperature sensor
when heating mode.
System fault
E4
23
The tube temperature is abnormal in cooling or heating
indoor fan fault
E6
2128
Indoor fan stop or run abnormally
Outdoor temperature
E7
9
Open circuit or short circuit of outdoor room temperature sensor
sensor fault
Exhaust temperature
E8
11
Open circuit or short circuit of outdoor exhaust gas temperature
sensor
sensor
Variable frequency drive
E9
1430
The driver module protect happen three times in 30 minutes.
module fault
Outdoor fan fault
EF
1620
Outdoor DC fan motor stop or run abnormally
Current sensor fault
EA
13
System can't collect current data normally.
Indoor EEPROM fault
EE
27
EEPROM data receive failed
Outdoor EEPROM fault
EE
19
PCB can't collect EEPROM data normally.
Compressor housing top
EP
8
The temperature of compressor housing top is more high or
switch fault
temperature switch fault
Voltage sensor fault
EU
12
System can't collect current voltage data normally.
Back gas temperature
EH
18
Open circuit or short circuit of outdoor exhaust gas temperature
sensor
sensor
power off Instantly
55
Instant power off
compressor input voltage
34
Compressor input voltage lack of phase
lost phase
High pressure protect
P3
24
High pressure protect
Model matching error
29
Capacity matching error
P1: Protection shutdown when voltage is higher than 275V or lower than 160V
Treatment Method: (voltage detection circuit in the inverter module board)
1. Use the multi‐meter to test whether the power supply between Phases A, B and C and Neutral Line is among
180V‐260V;
2. Whether the module communication line is reliably connected with the communication interface of main
control panel;
3. Whether the power supply module is reliably connected with filter boards L and N;
4. Replace the inverter module board;
5. Replace the motherboard of outdoor unit
P4: Inverter Compressor Exhaust High Temperature Protection
Treatment Method:
1. Test whether the compressor exhaust temperature is normal (below 115°);
2. If it is normal, please test whether the resistance of exhaust temperature sensor is consistent
with that in attached page (Annex 4);
99/ 113

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the TCL TCA-60HRA/DV3O and is the answer not in the manual?

TCL TCA-60HRA/DV3O Specifications

General IconGeneral
BrandTCL
ModelTCA-60HRA/DV3O
CategoryAir Conditioner
LanguageEnglish

Related product manuals