EasyManua.ls Logo

TDE MACNO DVS200 - Mains Input Current; Output

TDE MACNO DVS200
134 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
18 Chapter 3 - Description, Components and Specifications User Manual
Table 3.3.2.1-A: I/O specifications for drive models in Kw/Hp at 230 V
DVS Drive Type - Hp rating 025 037 055 075
OUTPUT
Inverter Output (IEC 146 class1), Continuous service
(@230V)
[kVA]
0,77 1,10 1,43 1,87
Inverter Output (IEC 146 class2), 150% overload for 60s
(@230V)
[kVA]
0,70 1,00 1,30 1,70
P
N
mot (recommended motor output):
@U
LN
=230Vac; f
SW
=default; IEC 146 class 1
[kW]
0,25 0,35 0,55 0,75
@U
LN
=230Vac; f
SW
=default; IEC 146 class 2
[kW]
0,25 0,35 0,55 0,75
@U
LN
=230Vac; f
SW
=default; IEC 146 class 1
[Hp]
0,35 0,50 0,75 1,00
@U
LN
=230Vac; f
SW
=default; IEC 146 class 2
[Hp]
0,35 0,50 0,75 1,00
U
2
Max output voltage
[V]
f
2
Max output frequency (*)
[Hz]
I
2N
Rated output current :
@U
LN
=230Vac; f
SW
= default; IEC 146 class 1
[A]
1,5 2,4 3,3 4,3
@U
LN
=230Vac; f
SW
=default; IEC 146 class 2
[A]
1,4 2,2 3,0 3,9
f
SW
switching frequency (Default)
[kHz]
f
SW
switching frequency (Higher)
[kHz]
Derating factor:
K
T
for ambient temperature
K
F
for switching frequency
INPUT
U
LN
AC Input voltage
[V]
AC Input frequency
[Hz]
I
N
AC Input current for continuous service :
- Connection without 3-phase reactor
@ 230Vac; IEC 146 class 1
[A]
3,0 4,5 6,0 8,0
Max short circuit power without line reactor (Zmin=1%)
[kVA]
Overvoltage threshold
[V]
Undervoltage threshold
[V]
0.94 x ULN (AC Input voltage)
500
12
18
410VDC (@ 230VAC)
230VDC (@ 230VAC)
0.8 @ 50°C (122°F)
0.7 for higher f
sw
220 V -15% 240 V +10%, 1-PHASE
50/60 Hz ±5%
3.3.3. Mains input current
The mains input current to the drive depends on the duty status of the controlled motor. Table 3.3.2.1
shows nominal continuous duty values (IEC 146 class 1) with typical output power factors for each
model of drive.
3.3.4. Output
The output from DVS drives is protected against short circuits between phases and to ground.
NOTA!
It is forbidden to connect any external voltage to the drives output terminals! Nevertheless, once a motor
has been disabled, it can be disconnected from the drive output while the drive is still functioning.
The nominal continuous output current value (I
CONT
) depends on mains voltage (Kv), ambient temperature (K
T
) and switching
frequency (K
F
) if higher than the default frequency:
I
CONT
= I
2N
x K
V
x K
T
x K
sw
(see table 3.3.2.1 for reduction factors), with a maximum overload capacity of I
MAX
= 1.5 x I
CONT
for 60 seconds.

Table of Contents

Related product manuals