10-5. About D/A Output Error
This is an error which is output only when D/A option is provided.
D/A output is less than the range of output.
For current output: 4mA - 25% or less (about 0mA or less)
For voltage output: 0V - 25% or less (about -2.5V or less)
The D/A output exceeds the range of the output.
For current output: 20mA + 25% or more (about 24mA or more)
For voltage output: 10V + 25% or more (about 12.5V or more)