TD350 Series VFD Basic operation instructions
-106-
Spindle scale-division completed
Output is valid when spindle scale-division is
completed
Output is valid when the frequency is limited
Virtual terminal output of
EtherCAT/PROFINET/Ethernet IP
communication
The corresponding signal is output according to
the set value of PROFINET communication.
When it is set to 1, the ON signal is output, and
when it is set to 0, the OFF signal is output.
Speed/position control switch-over
completed
Output is valid when the mode switch-over is
completed
C_Y1 from PLC (You need to set P27.00 to 1.)
C_Y2 from PLC (You need to set P27.00 to 1.)
C_HDO from PLC (You need to set P27.00 to 1.)
C_RO1 from PLC (You need to set P27.00 to 1.)
C_RO2 from PLC (You need to set P27.00 to 1.)
C_RO3 from PLC (You need to set P27.00 to 1.)
C_RO4 from PLC (You need to set P27.00 to 1.)
Related parameter list:
Detailed parameter description
0: Open collector high-speed pulse output
1: Open collector output
0: Invalid
1: In running
2: In forward running
3: In reverse running
4: In jogging
5: VFD fault
6: Frequency level detection FDT1
7: Frequency level detection FDT2
8: Frequency reached
9: Running in zero speed
10: Reach upper limit frequency
11: Reach lower limit frequency
12: Ready to run
13: In pre-exciting
Relay RO1 output
selection
Relay RO2 output
selection