TD350 Series VFD Function parameter list
-131-
by setting P07.00 to 0; if P01.00 is set to a non-zero value, the parameter will be protected by
password. When modifying function parameters through serial communication, the function of user
password also follows above rules.
Detailed parameter description
P00 group Basic functions
0: SVC 0 - Sensorless Vector Control mode 0
1: SVC 1 - Sensorless Vector Control mode 1
(recommended SVC mode)
2: V/F (SVPWM) - Sensorless Vector Pulse Width
Modulation
3: VC - Vector Control
Note: If 0, 1 or 3 is selected, it is required to carry
out motor parameter autotuning first.
0: Keypad
1: Terminal
2: Communication
Communication
running
command
channel
0: Modbus/Modbus TCP
1: PROFIBUS/CANopen/DeviceNet
2: Ethernet
3: EtherCAT/PROFINET/Ethernet IP
4: PLC programmable card
5: Wireless communication card
Note: 1, 2, 3, 4 and 5 are extended functions which
are applicable with corresponding cards.
Used to set the maximum output frequency of the
VFD. It is the basis of frequency setting and the
acceleration/deceleration.
Setting range: Max. (P00.04, 10.00) –630.00Hz
Upper limit of
running
frequency
The upper limit of running frequency is upper limit
value of VFD output frequency. This value cannot
be more than the maximum output frequency.
When the set frequency is higher than the upper
limit frequency, the VFD runs at the upper limit
frequency.
Setting range: P00.05–P00.03 (Max. output
frequency)
Lower limit of
running
frequency
The lower limit of running frequency is the lower
limit value of VFD output frequency.
When the set frequency is lower than the lower limit