TD350 Series VFD Function parameter list
-132-
Function
code
Name
Detailed parameter description
Default
value
Modify
frequency, the VFD runs at the lower limit
frequency.
Note: Max. output frequency upper limit
frequency ≥ lower limit frequency.
Setting range: 0.00HzP00.04 (upper limit of
running frequency)
P00.06
A frequency
command
selection
0: Set via keypad
1: Set via AI1
2: Set via AI2
3: Set via AI3
4: Set via high speed pulse HDIA
5: Set via simple PLC program
6: Set via multi-step speed running
7: Set via PID control
8: Set via Modbus/Modbus TCP communication
9: Set via PROFIBUS / CANopen / DeviceNet
communication
10: Set via Ethernet communication
11: Set via high speed pulse HDIB
12: Set via pulse string AB
13: Set via EtherCAT/PROFINET/Ethernet IP
communication
14: Set via PLC card
15: Reserved
0
P00.07
B frequency
command
selection
15
P00.08
Reference object
of B frequency
command
0: Max. output frequency
1: A frequency command
0
P00.09
Combination
mode of setting
source
0: A
1: B
2: (A+B)
3: (A-B)
4: Max. (A, B)
5: Min. (A, B)
0
P00.10
Set frequency via
keypad
When A and B frequency commands are set by
keypad, the value is the initial digital set value of the
VFD frequency.
Setting range: 0.00 HzP00.03 (Max. output
frequency)
60.00H
z