TD350 Series VFD Function parameter list
-140-
Function
code
Name
Detailed parameter description
Default
value
Modify
P01.27
Time of starting
section of
deceleration S
curve
0.0–50.0s
0.1s
◎
P01.28
Time of ending
section of
deceleration S
curve
0.0–50.0s
0.1s
◎
P01.29
Short-circuit
brake current
When the VFD starts in direct start mode
(P01.00=0), set P01.30 to a non-zero value to enter
short-circuit brake.
During stop, if the running frequency of VFD is
below the starting frequency of brake after stop, set
P01.31 to a non-zero value to enter short-circuit
brake after stop, and then carry out DC brake in the
time set by P01.12 (refer to P01.09–P01.12).
Setting range of P01.29: 0.0–150.0% (VFD)
Setting range of P01.30: 0.0–50.0s
Setting range of P01.31: 0.0–50.0s
0.0%
○
P01.30
Hold time of
short-circuit
brake at startup
0.00s
○
P01.31
Hold time of
short-circuit
brake at stop
0.00s
○
P01.32–
P01.34
Reserved
variables
0–65535
0
●
P02 group Parameters of motor 1
P02.00
Type of motor 1
0: Asynchronous motor
1: Synchronous motor
0
◎
P02.01
Rated power of
asynchronous
motor 1
0.1–3000.0kW
Depend
on
model
◎
P02.02
Rated frequency
of asynchronous
motor 1
0.01Hz–P00.03 (Max. output frequency)
60.00H
z
◎
P02.03
Rated speed of
asynchronous
motor 1
1–36000rpm
Depend
on
model
◎
P02.04
Rated voltage of
asynchronous
motor 1
0–1200V
Depend
on
model
◎
P02.05
Rated current of
asynchronous
motor 1
0.8–6000.0A
Depend
on
model
◎