EasyManua.ls Logo

TECHTOP TD350 - Page 146

TECHTOP TD350
371 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
TD350 Series VFD Function parameter list
-141-
Function
code
Name
Detailed parameter description
Default
value
Modify
P02.06
Stator resistance
of asynchronous
motor 1
0.001–65.53
Depend
on
model
P02.07
Rotor resistance
of asynchronous
motor 1
0.001–65.53
Depend
on
model
P02.08
Leakage
inductance of
asynchronous
motor 1
0.16553.5Mh
Depend
on
model
P02.09
Mutual
inductance of
asynchronous
motor 1
0.16553.5Mh
Depend
on
model
P02.10
No-load current
of asynchronous
motor 1
0.16553.5A
Depend
on
model
P02.11
Magnetic
saturation
coefficient 1 of
iron core of
asynchronous
motor 1
0.0100.0%
80.0%
P02.12
Magnetic
saturation
coefficient 2 of
iron core of
asynchronous
motor 1
0.0100.0%
68.0%
P02.13
Magnetic
saturation
coefficient 3 of
iron core of
asynchronous
motor 1
0.0100.0%
57.0%
P02.14
Magnetic
saturation
coefficient 4 of
iron core of
asynchronous
motor 1
0.0100.0%
40.0%

Table of Contents

Other manuals for TECHTOP TD350

Related product manuals