TD350 Series VFD Function parameter list
-142-
Function
code
Name
Detailed parameter description
Default
value
Modify
P02.15
Rated power of
synchronous
motor 1
0.1–3000.0KW
Depend
on
model
◎
P02.16
Rated frequency
of synchronous
motor 1
0.01Hz–P00.03 (Max. output frequency)
60.00H
z
◎
P02.17
Number of pole
pairs of
synchronous
motor 1
1–128
2
◎
P02.18
Rated voltage of
synchronous
motor 1
0–1200V
Depend
on
model
◎
P02.19
Rated current of
synchronous
motor 1
0.8–6000.0A
Depend
on
model
◎
P02.20
Stator resistance
of synchronous
motor 1
0.001–65.535Ω
Depend
on
model
○
P02.21
Direct-axis
inductance of
synchronous
motor 1
0.01–655.35mH
Depend
on
model
○
P02.22
Quadrature-axis
inductance of
synchronous
motor 1
0.01–655.35mH
Depend
on
model
○
P02.23
Counter-emf
constant of
synchronous
motor 1
0–10000
300
○
P02.24
Reserved
0x0000–0xFFFF
0
●
P02.25
Reserved
0%–50% (rated motor current)
10%
●
P02.26
Overload
protection of
motor 1
0: No protection
1: Common motor (with low-speed compensation).
As the cooling effect of common motor will be
degraded in low speed, the corresponding
electronic thermal protection value should also be
2
◎