TD350 Series VFD Function parameter list
-146-
Function
code
Name
Detailed parameter description
Default
value
Modify
above)
11: Set via EtherCAT/PROFINET/Ethernet IP
communication
12: Set via PLC
P03.12
Torque set by
keypad
-300.0%300.0% (rated motor current)
20.0%
P03.13
Torque reference
filter time
0.00010.000s
0.010s
P03.14
Source of upper
limit frequency
setting of forward
rotation in torque
control
0: Keypad (P03.16)
1: AI1 (100% corresponds to max. frequency)
2: AI2 (the same as above)
3: AI3 (the same as above)
4: Pulse frequency HDIA (the same as above)
5: Multi-step (the same as above)
6: Modbus/Modbus TCP communication (the same
as above)
7: PROFIBUS /CANopen/ DeviceNet
communication (the same as above)
8: Ethernet communication (the same as above)
9: Pulse frequency HDIB (the same as above)
10: EtherCAT/PROFINET/Ethernet IP
communication
11: PLC
12: Reserved
0
P03.15
Source of upper
limit frequency
setting of reverse
rotation in torque
control
0: Keypad (P03.17)
1: AI1 (100% corresponds to max. frequency)
2: AI2 (the same as above)
3: AI3 (the same as above)
4: Pulse frequency HDIA (the same as above)
5: Multi-step (the same as above)
6: Modbus/Modbus TCP communication (the same
as above)
7: PROFIBUS /CANopen/ DeviceNet
communication (the same as above)
8: Ethernet communication (the same as above)
9: Pulse frequency HDIB (the same as above)
10: EtherCAT/PROFINET/Ethernet IP
communication
11: PLC
0