TD350 Series VFD Function parameter list
-157-
Detailed parameter description
Current setting in
IF mode for
asynchronous
motor 1
When IF control is adopted for asynchronous motor
1, this parameter is used to set the output current.
The value is a percentage in relative to the rated
current of the motor.
Setting range: 0.0–200.0%
Proportional
coefficient in IF
mode for
asynchronous
motor 1
When IF control is adopted for asynchronous motor
1, this parameter is used to set the proportional
coefficient of the output current closed-loop control.
Setting range: 0–5000
Integral
coefficient in IF
mode for
asynchronous
motor 1
When IF control is adopted for asynchronous motor
1, this parameter is used to set the integral
coefficient of the output current closed-loop control.
Setting range: 0–5000
Frequency
threshold for
switching off IF
mode for
asynchronous
motor 1
When IF control is adopted for asynchronous motor
1, this parameter is used to set the frequency
threshold for switching off the output current
closed-loop control. When the frequency is lower
than the value of this parameter, the current
closed-loop control in the IF control mode is
enabled; and when the frequency is higher than
that, the current closed-loop control in the IF control
mode is disabled.
Setting range: 0.00–20.00 Hz
Enable/disable IF
mode for
asynchronous
motor 2
Current setting in
IF mode for
asynchronous
motor 2
When IF control is adopted for asynchronous motor
2, this parameter is used to set the output current.
The value is a percentage in relative to the rated
current of the motor.
Setting range: 0.0–200.0%
Proportional
coefficient in IF
mode for
asynchronous
motor 2
When IF control is adopted for asynchronous motor
2, this parameter is used to set the proportional
coefficient of the output current closed-loop control.
Setting range: 0–5000