TD350 Series VFD Function parameter list
-166-
Function
code
Name
Detailed parameter description
Default
value
Modify
P05.40
Corresponding
setting of lower
limit frequency of
HDIA
-100.0%–100.0%
0.0%
○
P05.41
Upper limit
frequency of
HDIA
P05.39 –50.000KHz
50.000
KHz
○
P05.42
Corresponding
setting of upper
limit frequency of
HDIA
-100.0%–100.0%
100.0%
○
P05.43
HDIA frequency
input filter time
0.000s–10.000s
0.030s
○
P05.44
HDIB high-speed
pulse input
function selection
0: Set input via frequency
1: Reserved
2: Encoder input, it should be used in combination
with HDIA
0
◎
P05.45
Lower limit
frequency of
HDIB
0.000 KHz – P05.47
0.000
KHz
○
P05.46
Corresponding
setting of lower
limit frequency of
HDIB
-100.0%–100.0%
0.0%
○
P05.47
Upper limit
frequency of
HDIB
P05.45 –50.000KHz
50.000
KHz
○
P05.48
Corresponding
setting of upper
limit frequency of
HDIB
-100.0%–100.0%
100.0%
○
P05.49
HDIB frequency
input filter time
0.000s–10.000s
0.030s
○
P05.50
AI1 input signal
type
0: Voltage type
1: Current type
Note: You can set the AI1 input signal type through
the corresponding function code.
0
◎
P05.51–
P05.52
Reserved
variables
0–65535
0
●