TD350 Series VFD Function parameter list
-171-
Function
code
Name
Detailed parameter description
Default
value
Modify
Setting range of P06.20: 0.00V10.00V
Setting range of P06.21: 0.000s10.000s
P06.22
P06.26
Reserved
variables
065535
0
P06.27
Lower limit of
HDO output
-100.0%P06.29
0.00%
P06.28
Corresponding
HDO output of
lower limit
0.0050.00kHz
0.00kHz
P06.29
Upper limit of
HDO output
P06.27100.0%
100.0%
P06.30
Corresponding
HDO output of
upper limit
0.0050.00kHz
50.00
kHz
P06.31
HDO output filter
time
0.000s10.000s
0.000s
P06.32
P06.34
Reserved
variable
065535
0
P07 group HMI
P07.00
User password
065535
Set it to any non-zero value to enable password
protection.
00000: Clear previous user password and disable
password protection.
After user password becomes valid, if wrong
password is inputted, users will be denied entry. It is
necessary to keep the user password in mind.
Password protection will be effective one minute
after exiting function code edit state, and it will
display "0.0.0.0.0" if users press PRG/ESC key to
enter function code edit state again, users need to
input the correct password.
Note: Restoring to default values will clear user
password, use this function with caution.
0
P07.01
Reserved variables
/
/
P07.02
Function of keys
Range: 0x000x27
Ones: Function selection of QUICK/JOG key
0: No function
0x01

Table of Contents