TD350 Series VFD Function parameter list
-177-
Detailed parameter description
Jump frequency
amplitude 2
setting the jump frequency, and three jump
frequency points can be set. If the jump frequency
points are set to 0, this function will be invalid.
Set frequency f
Time t
Jump
frequency 2
1/2* jump amplitude 2
1/2* jump amplitude 2
Jump
frequency 1
1/2* jump amplitude 1
1/2* jump amplitude 1
Jump
frequency 3
1/2* jump amplitude 3
1/2* jump amplitude 3
Setting range: 0.00Hz–P00.03 (Max. output
frequency)
Jump frequency
amplitude 3
Amplitude of
wobbling
frequency
0.0–100.0% (relative to set frequency)
Amplitude of
jump frequency
0.0–50.0% (relative to amplitude of wobbling
frequency)
Rise time of
wobbling
frequency
Descend time of
wobbling
frequency
Switching
frequency of
acceleration/dec
eleration time
0.00–P00.03 (Max. output frequency)
0.00Hz: no switch-over
Switch to acceleration/deceleration time 2 if the
running frequency is larger than P08.19
Frequency
threshold of the
start of droop
control
Reference
frequency of
acceleration/dec
eleration time
0: Max. output frequency
1: Set frequency
2: 100Hz
Note: Valid for straight acceleration/deceleration
only
Output torque
calculation mode
0: Calculated based on torque current