TD350 Series VFD Function parameter list
-182-
Function
code
Name
Detailed parameter description
Default
value
Modify
P08.49
Low bit of initial
value of power
consumption
Setting range of P08.48: 059999 kWh (k)
Setting range of P08.49: 0.0999.9 kWh
0.0 kWh
P08.50
Flux braking
This function code is used to enable flux braking
function.
0: Invalid
100150: The larger the coefficient, the stronger
the brake intensity
The VFD enables motor to decelerate quickly by
increasing the motor flux which converts energy
generated during braking into thermal energy.
The VFD monitors motor state continuously even
during flux braking, thus flux braking can be applied
in motor stop or used to change motor speed. The
flux braking also carries the following advantages.
1) Brake immediately after sending stop command,
removing the need to wait for flux to attenuate.
2) Better cooling effect. During flux braking, the
stator current of the motor increases, while the rotor
current does not change, while the cooling effect of
stator is much more effective than that of the rotor.
0
P08.51
Current
regulation
coefficient on
input side
This function code is used to adjust the current
display value on the AC input side.
0.001.00
0.56
P08.52
STO lock
0: STO alarm lock
Alarm-lock means STO alarm must be reset after
state restoration when STO occurs.
1: STO alarm unlock
Alarm-unlock means when STO occurs, after state
restoration, STO alarm will disappear automatically.
0
P08.53
Bias value of
upper limit
frequency of
torque control
0.00 HzP00.03 (Max. output frequency)
Note: This parameter is valid only for the torque
control mode.
0.00Hz
P08.54
Acceleration/dec
eleration
selection of
upper limit
frequency of
torque control
0: No limit on acceleration or deceleration
1: Acceleration/deceleration time 1
2: Acceleration/deceleration time 2
3: Acceleration/deceleration time 3
4: Acceleration/deceleration time 4
0