TD350 Series VFD Function parameter list
-187-
Function
code
Name
Detailed parameter description
Default
value
Modify
P09.15
Acceleration/
deceleration time
of PID command
0.01000.0s
0.0s
P09.16
Filter time of PID
output
0.00010.000s
0.000s
P09.17
Reserved
variable
P09.18
Low-frequency
integral time
Refer to P09.05.
Setting range: 0.0010.00s
0.90s
P09.19
Low-frequency
differential time
Refer to P09.06.
Setting range: 0.0010.00s
0.00s
P09.20
Lower frequency
point for PID
parameter
switching
5.00 Hz
P09.21
Upper frequency
point for PID
parameter
switching
10.00
Hz
P09.22
P09.28
Reserved
variables
065536
0
P10 group Simple PLC and multi-step speed control
P10.00
Simple PLC
mode
0: Stop after running once; the VFD stops
automatically after running for one cycle, and it can
be started only after receiving running command.
1: Keep running in the final value after running
once; The VFD keeps the running frequency and
direction of the last section after a single cycle.
2: Cyclic running; the VFD enters the next cycle
after completing one cycle until receiving stop
command and stops.
0
P10.01
Simple PLC
memory selection
0: No memory after power down
1: Memory after power down; PLC memories its
running stage and running frequency before power
down.
0
P10.02
Multi-step speed 0
Setting range of the frequency in 0
th
15
th
sections
are -100.0100.0%, 100% corresponds to Max.
output frequency P00.03.
Setting range of the running time in 0
th
15
th
0.0%
P10.03
Running time of
0
th
step
0.0s(min)
P10.04
Multi-step speed 1
0.0%