TD350 Series VFD Function parameter list
-187-
Detailed parameter description
Acceleration/
deceleration time
of PID command
Filter time of PID
output
Low-frequency
integral time
Refer to P09.05.
Setting range: 0.00–10.00s
Low-frequency
differential time
Refer to P09.06.
Setting range: 0.00–10.00s
Lower frequency
point for PID
parameter
switching
Upper frequency
point for PID
parameter
switching
P10 group Simple PLC and multi-step speed control
0: Stop after running once; the VFD stops
automatically after running for one cycle, and it can
be started only after receiving running command.
1: Keep running in the final value after running
once; The VFD keeps the running frequency and
direction of the last section after a single cycle.
2: Cyclic running; the VFD enters the next cycle
after completing one cycle until receiving stop
command and stops.
Simple PLC
memory selection
0: No memory after power down
1: Memory after power down; PLC memories its
running stage and running frequency before power
down.
Setting range of the frequency in 0
th
–15
th
sections
are -100.0–100.0%, 100% corresponds to Max.
output frequency P00.03.
Setting range of the running time in 0
th
–15
th