TD350 Series VFD Function parameter list
-188-
Detailed parameter description
sections are 0.0–6553.5s (min), the time unit is
determined by P10.37.
When simple PLC operation is selected, it is
required to set P10.02–P10.33 to determine the
running frequency and running time of each
section.
Note: The symbol of multi-step speed determines
the running direction of simple PLC, and the
negative value means reverse running.
P10.02
P10.04
P10.06
P10.32
P10.30
P10.28
Deceleration time
(two sections)
Acceleration time
(two sections)
P10.03 P10.05 P10.07 P10.31 P10.33
When selecting multi-step speed running, the
multi-step speed is within the range of -fmax–fmax,
and it can be set continuously. The start/stop of
multi-step stop is also determined by P00.01.
TD350 series VFD can set 16-step speed, which
are set by combined codes of multi-step terminals
1–4 (set by S terminal, correspond to function code
P05.01–P05.06) and correspond to multi-step
speed 0 to multi-step speed 15.