TD350 Series VFD Function parameter list
-190-
Detailed parameter description
Select corresponding acceleration/deceleration
time, and then convert 16-bit binary number into
hexadecimal number, finally, set corresponding
function code.
Acceleration/deceleration time 1 is set by P00.11
and P00.12; Acceleration/deceleration time 2 is set
by P08.00 and P08.01; Acceleration/deceleration
time 3 is set by P08.02 and P08.03; Acceleration
/deceleration time 4 is set by P08.04 and P08.05.
Setting range: 0x0000–0xFFFF
0: Restart from the first step, namely if the VFD
stops during running (caused by stop command,
fault or power down), it will run from the first step
after restart.
1: Continue running from the step frequency when
interruption occurred, namely if the VFD stops
during running (caused by stop command or fault),
it will record the running time of current step, and
enters this step automatically after restart, then
continue running at the frequency defined by this
step in the remaining time.
0: s; the running time of each step is counted in
seconds;
1: min; the running time of each step is counted in
minutes;
P11 group Protection parameters
0x000–0x111
Ones:
0: Disable software input phase loss protection
1: Enable software input phase loss protection
Tens:
0: Disable output phase loss protection
1: Enable output phase loss protection
Hundreds:
0: Disable hardware input phase loss protection
1: Enable hardware input phase loss protection
Frequency-drop
at transient
power down