TD350 Series VFD Function parameter list
-191-
Function
code
Name
Detailed parameter description
Default
value
Modify
P11.02
Reserved
variables
065535
0
P11.03
Overvoltage stall
protection
0: Disable
1: Enable
Overvoltage stall
threshold
Output
frequency
Time t
Time t
DC bus voltage V
1
P11.04
Overvoltage stall
protection
voltage
120150% (standard bus voltage) (220V)
120%
120150% (standard bus voltage) (460V)
120%
120150% (standard bus voltage) (575V)
120%
P11.05
Current-limit
selection
During accelerated running, as the load is too large,
the actual acceleration rate of motor is lower than
that of output frequency, if no measures are taken,
the VFD may trip due to overcurrent during
acceleration.
0x000x11
Ones: Current-limit action selection
0: Invalid
1: Always valid
Tens: Hardware current-limit overload alarm
selection
0: Valid
1: Invalid
01
P11.06
Automatic
current-limit level
Current-limit protection function detects output
current during running, and compares it with the
current-limit level defined by P11.06, if it exceeds
the current-limit level, the VFD will run at stable
frequency during accelerated running, or run in
decreased frequency during constant-speed
running; if it exceeds the current-limit level
continuously, the VFD output frequency will drop
continuously until reaching lower limit frequency.
When the output current is detected to be lower
G
model:
160.0%
P
model:
120.0%
P11.07
Frequency-drop
rate during
current limit
10.00
Hz/s