TD350 Series VFD Function parameter list
-200-
Detailed parameter description
This parameter is used to set the pulse current
threshold when the initial magnetic pole position is
detected in the pulse mode. The value is a
percentage in relative to the rated current of the
motor.
Setting range: 0.0–300.0% (of the rated voltage of
the motor)
This parameter is used to set the frequency
threshold for enabling the counter-electromotive
force phase-locked loop in SVC 0. When the
running frequency is lower than the value of this
parameter, the phase-locked loop is disabled; and
when the running frequency is higher than that, the
phase-locked loop is enabled.
Setting range: 0–655.35
Maladjustment
detection time
This parameter is used to adjust the
responsiveness of anti-maladjustment function. If
the load inertia is large, increase the value of this
parameter properly, however, the responsiveness
may slow down accordingly.
Setting range: 0.0–10.0s
High-frequency
compensation
coefficient of
synchronous
motor
This parameter is valid when the motor speed
exceeds the rated speed. If motor oscillation
occurred, adjust this parameter properly.
Setting range: 0.0–100.0%
P14 group Serial communication function
Local
communication
address
Setting range: 1–247
When the master is writing frames, and the slave
communication address is set to 0, it is the