0: Invalid
1: Fire mode 1
2: Fire mode 2
P28.25=0, the fire mode is invalid. The inverter runs
in normal mode and stops at fault. When P28.25 is
non-zero and the fire signal is enabled, the fire
mode will be valid. The VFD will run in the
frequency P28.26.
Fire mode 1, the VFD will keep running unless it is
damaged.
Fire mode 2, the VFD will keep running except
OUT1, OUT2, OUT3, OC1, OC2, OC3, OV1, OV2,
OV3 and SPO faults.
Note: Terminal control is required for fire mode
function
0~1
After the inverter runs in fire mode for 5 minutes, set
the flag bit without warranty handling.