TD350 Series VFD Function parameter list
-238-
Function
code
Name
Detailed parameter description
Default
value
Modify
mode / torque
mode switching
frequency point
P28.06
Number of slaves
015
1
P28.25
Fire mode
0: Invalid
1: Fire mode 1
2: Fire mode 2
P28.25=0, the fire mode is invalid. The inverter runs
in normal mode and stops at fault. When P28.25 is
non-zero and the fire signal is enabled, the fire
mode will be valid. The VFD will run in the
frequency P28.26.
Fire mode 1, the VFD will keep running unless it is
damaged.
Fire mode 2, the VFD will keep running except
OUT1, OUT2, OUT3, OC1, OC2, OC3, OV1, OV2,
OV3 and SPO faults.
Note: Terminal control is required for fire mode
function
0
P28.26
Running
frequency in fire
mode
0.00Hz~P00.03 (Max. output frequency)
50Hz
P28.27
Fire mode flag bit
0~1
After the inverter runs in fire mode for 5 minutes, set
the flag bit without warranty handling.
0
P28.28
P28.29
Reserved
variables
065535
0
P90 group Customized function group 1
P90.00
P90.39
Reserved
variables
065535
0
P91 group Customized function group 2
P91.00
P91.39
Reserved
variables
065535
0
P92 group Customized function group 3
P92.00
P92.39
Reserved
variables
065535
0
P93 group Customized function group 4
P93.00
P93.39
Reserved
variables
065535
0