TD350 Series VFD Function parameter list
-237-
Detailed parameter description
Corresponding
AO3 output of
upper limit
Setting range of P26.41: 0.00V–10.00V
Setting range of P26.42: 0.000s–10.000s
Setting range of P26.43: -100.0%–P26.45
Setting range of P26.44: 0.00V–10.00V
Setting range of P26.45: P26.43–100.0%
Setting range of P26.46: 0.00V–10.00V
Setting range of P26.47: 0.000s–10.000s
P28 group Master/slave control functions
Master/slave
mode selection
0: The master/slave control is invalid
1: This machine is a master
2: This machine is a slave
Master/slave
communication
data selection
Master/slave
control mode
Ones: Master/slave running mode selection
0: Master/slave mode 0
(The master and slave adopt speed control and
maintains the power balance by droop control)
1: Master/slave mode 1
(The master and slave must be in the same type of
vector control mode. The master is speed control,
and the slave will be forced to be in the torque
control mode.
2: Master/slave mode 2
Start in the slave first speed mode (master/slave
mode 0) and then switch to torque mode at a
certain frequency point (master/slave mode 1)
Tens: Slave start command source selection
0: Follow the master to start
1: Determined by P00.01
Hundreds: Slave transmitting/master receiving data
enable
0: Enable
1: Disable
Master/slave
mode 2 speed