TD350 Series VFD Installation guidelines
-31-
Input impedance: 20kΩ during voltage input; 250Ω during current input;
AI1 voltage or current input is set by P05.50;
Resolution ratio: When 10V corresponds to 50Hz, the min. resolution ratio is
5mV;
25°C, When input above 5V or 10mA, the error is ±0.5%
+10.5V reference zero potential
Output range: 0–10V voltage or 0–20mA current
Voltage or current output is set by toggle switch SW2;
25°C , when input above 5V or 10mA, the error is ±0.5%.
RO1 relay output; RO1A is NO, RO1B is NC, RO1C is common port
Contact capacity: 3A/AC250V, 1A/DC30V
RO2 relay output; RO2A is NO, RO2B is NC, RO2C is common port
Contact capacity: 3A/AC250V, 1A/DC30V
Switch capacity: 200mA/30V;
Range of output frequency: 0–50kHz
Duty ratio: 50%
Common port of open collector output; short connected to COM by default
1. Switch capacity: 200mA/30V;
2. Range of output frequency: 0–1kHz
485 communication port, 485 differential signal port and standard 485
communication interface should use twisted shielded pair; the 120ohm terminal
matching resistor of 485 communication is connected by toggle switch SW3.
Provide input digital working power from external to internal;
Voltage range: 12–24V
The VFD provides user power; the maximum output current is 200mA
Internal impedance: 3.3kΩ
Accept 12–30V voltage input
This terminal is bi-directional input terminal and supports
NPN/PNP connection modes
Max. input frequency: 1kHz
All are programmable digital input terminals, users can set the
terminal function via function codes
Besides S1–S4 functions, it can also act as high frequency pulse input channel
Max. input frequency: 50kHz;