TD350 Series VFD Basic operation instructions
-54-
The running command channel can be set by terminal commands besides P00.01 and P00.02.
Current running
command channel
P00.01
Multi-function
terminal function (36)
Command switches
to keypad
Multi-function terminal
function (37)
Command switches to
terminal
Multi-function terminal
function (38)
Command switches to
communication
Keypad
/
Terminal
Communication
Terminal
Keypad
/
Communication
Communication
Keypad
Terminal
/
Note: "/" means this multi-function terminal is valid under current reference channel.
Related parameter list:
Function
code
Name
Detailed parameter description
Default
value
P00.00
Speed control mode
0: SVC 0 - Sensorless Vector Control mode 0
1: SVC 1 - Sensorless Vector Control mode 1
(recommended SVC mode)
2: V/F (SVPWM) - Sensorless Vector Pulse
Width Modulation
3: VC - Vector Control
Note: If 0, 1 or 3 is selected, it is required to
carry out motor parameter autotuning first.
2
P00.01
Running command
channel
0: Keypad
1: Terminal
2: Communication
0
P00.02
Communication running
command channel
0:Modbus/Modbus TCP
1:PROFIBUS/CANopen/DeviceNet
2:Ethernet
3:EtherCAT/PROFINET/Ethernet IP
4:PLC programmable card
5:Bluetooth card
0
P00.15
Motor parameter
autotuning
0: No operation
1: Rotary autotuning; carry out
comprehensive motor parameter autotuning;
rotary autotuning is used in cases where high
control precision is required;
2: Static autotuning 1 (comprehensive
autotuning); static autotuning 1 is used in
cases where the motor cannot be
disconnected from load;
3: Static autotuning 2 (partial autotuning) ;
0