TD350 Series VFD Basic operation instructions
-68-
Detailed parameter description
0.0%–P04.31 (rated motor voltage)
Flux-weakening
coefficient in the
constant power zone
Input current 1 in
synchronous motor
V/F control
When the synchronous motor V/F control mode is
enabled, this parameter is used to set the reactive
current of the motor when the output frequency is
lower than the frequency set in P04.36.
Setting range: -100.0%–+100.0% (of the rated
current of the motor)
Input current 2 in
synchronous motor
V/F control
When the synchronous motor V/F control mode is
enabled, this parameter is used to set the reactive
current of the motor when the output frequency is
higher than the frequency set in P04.36.
Setting range: -100.0%–+100.0% (of the rated
current of the motor)
Frequency threshold
for input current
switching in
synchronous motor
V/F control
When the synchronous motor V/F control mode is
enabled, this parameter is used to set the
frequency threshold for the switching between input
current 1 and input current 2.
Setting range: 0.00 Hz–P00.03 (Max. output
frequency)
Reactive current
closed-loop
proportional
coefficient in
synchronous motor
V/F control
When the synchronous motor V/F control mode is
enabled, this parameter is used to set the
proportional coefficient of the reactive current
closed-loop control.
Setting range: 0–3000
Reactive current
closed-loop integral
time in synchronous
motor V/F control
When the synchronous motor V/F control mode is
enabled, this parameter is used to set the integral
coefficient of the reactive current closed-loop
control.
Setting range: 0–3000
Reactive current
closed-loop output
limit in synchronous
When the synchronous motor V/F control mode is
enabled, this parameter is used to set the output
limit of the reactive current closed-loop control. A