TD350 Series VFD Basic operation instructions
-69-
Detailed parameter description
greater value indicates a higher reactive
closed-loop compensation voltage and higher
output power of the motor. In general, you do not
need to modify this parameter.
Setting range: 0–16000
Enable/disable IF
mode for
asynchronous motor 1
Current setting in IF
mode for
asynchronous motor 1
When IF control is adopted for asynchronous motor
1, this parameter is used to set the output current.
The value is a percentage in relative to the rated
current of the motor.
Setting range: 0.0–200.0%
Proportional
coefficient in IF mode
for asynchronous
motor 1
When IF control is adopted for asynchronous motor
1, this parameter is used to set the proportional
coefficient of the output current closed-loop control.
Setting range: 0–5000
Integral coefficient in
IF mode for
asynchronous motor 1
When IF control is adopted for asynchronous motor
1, this parameter is used to set the integral
coefficient of the output current closed-loop control.
Setting range: 0–5000
Frequency threshold
for switching off IF
mode for
asynchronous motor 1
When IF control is adopted for asynchronous motor
1, this parameter is used to set the frequency
threshold for switching off the output current
closed-loop control. When the frequency is lower
than the value of this parameter, the current
closed-loop control in the IF control mode is
enabled; and when the frequency is higher than
that, the current closed-loop control in the IF control
mode is disabled.
Setting range: 0.00–20.00 Hz
Enable/disable IF
mode for
asynchronous motor 2
Current setting in IF
mode for
asynchronous motor 2
When IF control is adopted for asynchronous motor
2, this parameter is used to set the output current.
The value is a percentage in relative to the rated
current of the motor.
Setting range: 0.0–200.0%