4-120
06- 30 Operation time setting of speed-stage 14
06- 31 Operation time setting of speed-stage 15
Range
【
0.0~6000.0】Sec
06- 32 Operation direction selection of speed-stage 0
06- 33 Operation direction selection of speed-stage 1
06- 34 Operation direction selection of speed-stage 2
06- 35 Operation direction selection of speed-stage 3
06- 36 Operation direction selection of speed-stage 4
06- 37 Operation direction selection of speed-stage 5
06- 38 Operation direction selection of speed-stage 6
06- 39 Operation direction selection of speed-stage 7
06- 40 Operation direction selection of speed-stage 8
06- 41 Operation direction selection of speed-stage 9
06- 42 Operation direction selection of speed-stage 10
06- 43 Operation direction selection of speed-stage 11
06- 44 Operation direction selection of speed-stage 12
06- 45 Operation direction selection of speed-stage 13
06- 46 Operation direction selection of speed-stage 14
06- 47
Operation direction selection of speed-stage 15
Range
【0】: Stop 【1】: Forward 【2】: Reversal
The automatic operation mode can be achieved by using command setting
(05-01,06-01~06-15) of multi-step speed frequency reference,and at the same time
linked to the time setting of automatic operation mode automatically (06-16~06-31),
with the use of automatic operation setting for selection (06-00). This automatic
operation orientation can be set by parameter 06-32~06-47.
. The automatic operation mode will be invalid if the following functions are enabled:
1. Frequency wobbling function
2. PID function
. In automatic operation mode, the multi-step speed reference
command1~4(03-00~03-07=2~5) of external terminal is invalid.
Example of automatic operation mode:
(1) Single cycle operation (06-00 = 1,4)
Under the special setting, the inverter will perform a single cycle for operation and
then stop.
Figure 4.3.52 Single cycle automatic operation (stop)
Parameter setting of cycle operation
06-00 =1(single cycle automatic operation mode)
06-32~06-34 =1(Forward for multi-step speed 0 - 2)
06-35 =2(Reversal for multi-step speed 3)
06-36~06-47 =0(Stop for multi-step speed 4 - 15)
05-01 =15 Hz(Multi-step speed 0:15 Hz)
06-01 =30 Hz(Multi-step speed 1:30 Hz)
06-02 =50 Hz(Multi-step speed 2:50 Hz)
06-03 =20 Hz(Multi-step speed 0:20 Hz)
06-16 =20 sec(Multi-step speed 0:20 sec)
06-17 =25 sec(Multi-step speed 1:25 sec)
06-18 =30 sec(Multi-step speed 2:30 sec)
06-19 =40 sec(Multi-step speed 3:40 sec)