EasyManua.ls Logo

TECO A510-2001-H - Page 193

TECO A510-2001-H
311 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4-139
. Setting Example of less torque detection:
Inverter output current
( or motor output torque )
Detect level 1(08-19)
Undertorque
detection
signal
t
t
08-20
08-20
10% hystersis
width
Figure 4.3.74 Less torque detection operation
08- 23
Ground Fault (GF) selection
Range
0:
Invalid
1: V
alid
Ground Fault (GF) protection selection (08-23)
. Adjust 08-23 to enable or disable the ground Fault (GF) protection
08-23 =0: Disable the ground Fault (GF) protection
= 1: Enable the ground Fault (GF) protection
. If the inverter leakage current closes to 50% of inverter rated current and the ground
failure function is enabled (08-23), the digital operator will display the failure message of
"GF Ground Fault" (GF), failure contact acts and the inverter will coast to stop.
08- 24
External Fault Operation Selection
Range
0:
Deceleration to stop
1:
Coast to stop
2: continuous operation
08- 25
Detection selection of external fault
Range
0:
Immediately detect when the power is supplied.
1:
Start to detect when the operation is started.

Table of Contents

Related product manuals