4-140
09- Communication Function Group
09- 00
INV Communication Station Address
Range
【
1~31】
09- 02 Baud rate setting (bps)
Range
【0】:
1200
【1】:
2400
【2】:
4800
【3】:
9600
【4】: 19200
【5】: 38400
09- 03
Stop bit selection
Range
【0】:
1 stop bit 【1】: 2 stop bit
09- 04
Parity selection
Range
【0】:
no Parity
【1】: even bit
【2】:
odd bit
09- 06
Communication error detection time
Range
【
0.0~25.5】Sec
09- 07
Fault stop selection
Range
【0】: Decceleration to stop based on deceleration time 1 when communication fault
occurs.
【1】: Coast to stop when communication fault occurs.
【2】: Decceleration to stop based on deceleration time 2 when communication fault
occurs.
【3】: Keep operating when communication fault occurs.
09- 09
Waiting time
Range
【
5~65】mSec
Modbus (RS-485) communication port RJ45 (S (+),S (-))built in the inverter can be used
to monitor the status of the inverter, read and set parameters
. Modbus communication can perform the following operations, regardless of the
settings of 00-05 (Frequency Command Selection) and 00-02 (Operation Command
Selection).
─ Monitor the operation situation by the controller (PLC)
─ Set and read parameters.
─ Re-start error.
─ Input multi-function command