4-140
09- Communication Function Group
09- 00
INV Communication Station Address
Range
1~31
09- 02 Baud rate setting (bps)
Range
0:
1200
1:
2400
2:
4800
3:
9600
4: 19200
5: 38400
09- 03
Stop bit selection
Range
0:
1 stop bit 1: 2 stop bit
09- 04
Parity selection
Range
0:
no Parity
1: even bit
2:
odd bit
09- 06
Communication error detection time
Range
0.0~25.5Sec
09- 07
Fault stop selection
Range
0: Decceleration to stop based on deceleration time 1 when communication fault
occurs.
1: Coast to stop when communication fault occurs.
2: Decceleration to stop based on deceleration time 2 when communication fault
occurs.
3: Keep operating when communication fault occurs.
09- 09
Waiting time
Range
5~65mSec
Modbus (RS-485) communication port RJ45 (S (+),S (-))built in the inverter can be used
to monitor the status of the inverter, read and set parameters
. Modbus communication can perform the following operations, regardless of the
settings of 00-05 (Frequency Command Selection) and 00-02 (Operation Command
Selection).
Monitor the operation situation by the controller (PLC)
Set and read parameters.
Re-start error.
Input multi-function command