4-177
■ READ: Use the following steps to store the parameter settings of the inverter to the
operation interface of the digital operator.
Steps
Screen display
(English)
Description
1
Select the copy function group (16) from the groups menu.
2
Press the Data / Enter key and select the parameter (16-07)
display of copy function.
3
Press the Data / Enter key to display the data setting / read
screen (the digital is reversed video and flicker).
4
Change the set value to 1 (read) by using increase key.
5
. Use data/enter key to enable the read operation, the display
is shown as the left.
. The bottom of LCD display will show a bar to indicate the
read progress.
-ADV-
READ
COMPLETE
“READ COMPLETE” will be displayed on the digital
operator interface after reading is successful.
6
. The error message of "RDP Read Prohibited" may occur in
the memory of the interface when storing the inverter
parameter settings to the digital operator.
. If the error is displayed, press any key to remove the error
message and back to the display 16-07.
7
. When DSP/FUN key is pressed, the display returns to the
sub-directory (16-07).