EasyManua.ls Logo

TECO A510-2001-H - Page 234

TECO A510-2001-H
311 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4-180
17- Automatic Tuning Function Group
17- 00
Mode selection of automatic tuning
Range
0: Rotation autotune
1: Static autotune
2: Stator resistance measurement (V / F)
17- 01
Motor rated output power
Range
0.00~600.00KW
17- 02
Motor rated current
Range
For VF, VF+PG modes, it is 10%~200% of the inverter rated current
For SLV, SV modes, it is 25%~200% of the inverter rated current.
17- 03
Motor rated voltage
Range
0.0~255.0V: 220V
0.0~510.0V: 440V
17- 04
Motor rated frequency
Range
10.0~400.0Hz
10.0~1200.0Hz (when 00-31 = 1)
17- 05
Motor rated speed
Range
0~24000rpm
17- 06
Pole number of motor
Range
2,4,6,8pole
17- 07
Number of PG pulse
Range
0~60000ppr
17- 08
Motor no-load voltage
Range
50~240V: 220V
100~480V: 440V
17- 09
Motor excitation current
Range
0.01~600.00A
17- 10
Automatic tuning start
Range
0: Invalid
1: Valid
17- 11
Error history of automatic tuning
Range
0: No error
1: Motor data error
2: Stator resistance tuning error
3: Leakage induction tuning error
4: Rotor resistance tuning error
5: Mutual induction tuning error
6: Encoder error
7: DT Error
8: Motor’s acceleration error
9: Warning
*1. Set value is for 220V class, the value of its two times is for 440V class.
*2.The set range from 0.0 to 400.0 Hz is for HD mode (00-27=0), and from 0.0 to
120.0Hz is for ND mode (00-27=1) , and from 0.0 to 1200.0Hz is high frequency mode
(00-31=1).
. Set motor nameplate’s rated output power (17-01), motor output rated current
(17-02), motor rated voltage (17-03),motor rated frequency (17-04),motor rated
speed (17-05) and motor’s pole number (17-06) and so on for automatic tuning
operation.

Table of Contents