4-179
■ Verify: Use the following steps to compare the inverter parameter to the set value of the
operation interface of digital operator.
16- 09
Selection of operator breaking off (LCD)
Range
【
0】: Display fault when LCD operator is broken off.
【
1】: Keep operating when LCD operator is broken off.
.In Local mode, when the digital operator is removed, this parameter determines whether
the inverter should be stopped or not.
Steps LCD Display (English) Description
1
Select the copy function group (16) from the groups menu.
2
Press the Data / Enter key and select the parameter (16-07)
display of copy function.
3
Press the Data / Enter key to display the data setting / read
screen (the digital is reversed video and flicker).
4
Change the set value to 3 (verify) by using increase key.
5
. Use data/enter key to enable the confirming operation, the
display is shown as the left.
. The bottom of LCD display will show a bar to indicate the
write-in progress.
-ADV-
VERIFY
COMPLETE
If data is successfully confirmed, the message of “VERIFY
COMPLETE” will display.
6
. An erro message of “VRYE Verify Error” may occur, please
confirm it.
. If the error is displayed, press any key to remove the error
message and back to the display 16-07.
7
when DSP/FUN key is pressed, the display returns to the
sub-directory (16-07)