4-16
Control mode
Code Parameter Name Range Default Unit
V/F
V/F
+PG
SLV SV
PM
SV
PM
SLV
Attrib
ute
03-08 (S1~S8)DI Scan time
0: Scan time 4ms
1: Scan time 8ms
1 - O O O O O O
xxx0b: S1 A contact xxx1b: S1
B contact
xx0xb: S2 A contact xx1xb: S2
B contact
x0xxb: S3 A contact x1xxb: S3
B contact
03-09
Multi-function terminal
S1-S4 type selection
0xxxb: S4 A contact1 xxxb: S4
B contact
0000b - O O O O O O
xxx0b: S5 A contact xxx1b: S5
B contact
xx0xb: S6 A contact xx1xb: S6
B contact
x0xxb: S7 A contact x1xxb: S7
B contact
03-10
Multi-function terminal
S5-S8 type selection
0xxxb: S8 A contact 1xxxb: S8
B contact
0000b - O O O O O O
03-11
Relay (R1A-R1C)
output
1 - O O O O O O
03-12
Relay (R2A-R2C)
output
0: Durning Running
1: Fault contact output
2: Frequency Agree
3: Setting Frequency Agree
4: Frequency detection 1 (>
03-13)
5: Frequency detection 2 (<
03-13)
6: Automatic restart
7: Retain
8: Retain
9: Baseblock
10: Retain
11: Retain
12: Over torque detection
13: Retain
14: Retain
15: Retain
16: Retain
17: Retain
18: PLC status
19: PLC control contact
20: zero speed
21: Inverter Ready
22: Undervoltage Detection
23: Source of operation
command
24: Source of frequency
command
25: Low torque detection
26: Frequency Reference
20 - O O O O O O