4-28
Control mode
Code Parameter Name Range Default Unit
V/F
V/F
+PG
SL
V
SV
PM
SV
PM
SL
V
Attrib
ute
xxx0b: Motor overload is
invalid.
xxx1b: Motor overload is valid.
xx0xb: Cold start of motor
overload
xx1xb: Hot start of moto
overload
x0xxb: Standard motor
x1xxb: Inverter motor
0xxxb: Retain
08-05
Selection for motor
overload protection
(OL1)
1xxxb: Retain
0001b - O O O O O O
0: stop output after overload
protection
08-06
Start-up mode of
overload protection
operation (OL1)
1: Continuous operation afte
overload protection.
0 - O O O O O O
08-07 Retain
0:Valid
08-08
utomatic voltage
regulation (AVR)
1: Invalid
0 - O O O O O O
0: Invalid
08-09
Selection of input
phase loss protection
1:Valid
0 - O O O O O O
0: Invalid
08-10
Selection of output
phase loss protection
1:Valid
0 - O O O O O O
08-11 Retain
08-12 Retain
0: Over-torque detection is
invalid.
1: Start to detect when
reaching the set frequency.
08-13
Selection of over-torque
detection
2: Start to detect when the
operation is begun.
0 - O O O O O O
0: Decceleration to stop when
over torque is detected.
08-14
Selection of over-torque
operation
1: Dispay warning when ove
torque is detected. Go on
operation.
0 - O O O O O O
08-15
Level of over-torque
detection
0~300 150 % O O O O O O
08-16
Time of over-torque
detection
0.0~10.0 0.1 Sec O O O O O O
0: Low-torque detection is
invalid.
1: Start to detect when
reaching the set frequency.
08-17
Selection of low-torque
detection
2: Start to detect when the
operation is begun.
0 - O O O O O O
08-18
Selection of low-torque
operation
0: Decceleration to stop when
low torque is detected.
0 - O O O O O O