TECO A510-2001-H - 08-13 Selection of over-torque detection

TECO A510-2001-H
311 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4-29
1: Dispay warning when low
torque is detected. Go on
operation.
08-19
Level of low-torque
detection
0~300 150 % O O O O O O
08-20
Time of low-torque
detection
0.0~10.0 0.1 Sec O O O O O O
08-21
Limit of stall
prevention in
acceleration
0~100 50 % O O O X X O
08-22
Stall prevention
detection time in
operation
2~100 100 ms O O O X X O
0: invalid
08-23 Ground Fault Selection
1: valid
0 - O O O O O O
0: Deceleration to stop
1: Coast to stop
08-24
External Fault
Operation Selection
2: continuous operation
0 - O O O O O O
0: Immediately detect when the
power is supplied.
08-25
Detection selection of
external fault
1: Start to detect when the
operation is started.
0 - O O O O O O
08-26 Retain
08-27 Retain
08-28 Retain
08-29 Retain
08-30 Retain
Group 09 Communication Function Group
Control mode
Attrib
ute
Code Parameter Name Range Default Unit
V/F
V/F
+PG
SLV SV
PM
SV
PM
SLV
09-00
INV Communication
Station Address
1~31 1 - O O O O O O *2
09-01 Retain
0:1200
1:2400
2:4800
3:9600
4:19200
09-02 Baud rate setting
3 - O O O O O O *2
0: 1stop bit
09-03 Stop bit selection
1: 2 stop bit
0 - O O O O O O *2
0: No Parity
1:even bit
09-04 Parity selection
2:odd bit
0 - O O O O O O *2
09-05 Retain