4-44 
Group 16 LCM Function Group 
Control mode 
Code  Parameter Name  Range  Default Unit
V/F 
V/F 
+PG 
SLV SV 
PM
SV
PM
SLV
Attrib
ute
Users specify the format, 
Inputing 1XXXX represents 
the display of X.XXX at 100%.
0: without using engineering
unit  
1: FPM 
2: CFM 
3: PSI 
4: GPH 
5: GPM 
6: IN 
7: FT 
8: /s 
9: /m 
10: /h 
11: °F 
12: inW 
13: HP 
14: m/s 
15: MPM 
16: CMM 
17: W 
18: KW 
19: m 
16-04 Engineering unit 
20: °C 
0  -  O O O O O X  
16-05 LCD backlight  0~7  5  -  O O O O O O *1
16-06 
utomatic return time  0~120  60  Sec O  O  O  O  O O *1
0: Do not copy parameters 
1: Read inverter parameters 
and save to the operator.   
2: Write the operator 
parameters to inverter.     
16-07 
Copy function
selection 
3: Compare parameters of 
inverter and operator.   
0  -  O O O O O O  
0: Do not allow to read inverter
parameters and save to the 
operator.   
16-08 
Selection of allowing
reading 
1: Allow to read inverter 
parameters parameters and 
save to the operator. 
0  -  O O O O O O  
0: Display fault when LCD 
operator is broken off.   
16-09 
Selection of operato