EasyManuals Logo

TECO E310 Series User Manual

TECO E310 Series
95 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #32 background imageLoading...
Page #32 background image
4-9
Function
Code No.
Description Range/Code
Factory
Setting
Remarks
04-03
Momentary Power Loss and
Restart
0 : Momentary Power Loss and Restart
disable
1 : Momentary power loss and restart
enable
2 : Momentary power loss and restart
enable while CPU is operating.
(According to the capacity of DC
power)
0
04-04
Momentary Power Loss
Ride-Thru Time (Seconds)
0.0 - 2.0 0.5
04-05 Auto Restart Method
0 :
Enable Speed Search
1 : Normal Start
0
04-06 Auto Restart Delay Time (Seconds) 0.0 - 800.0 0.0
04-07 Number of Auto Restart Attempts 0-10 0
04-08 Reset Mode Setting
0 : Enable Reset Only when Run
Command is Off
1 :
Enable Reset when Run
Command is On or Off
0
04-09 Direct Running After Power Up
0 :
Enable Direct running after power
up
1 :
Disable Direct running after power
up
1
04-10 Delay-ON Timer (Seconds) 1.8 ~300.0 1.0
04-11
Kinetic Energy
Back-up Deceleration Time
0.0 :
Disable
0.1~25.0KEB Deceleration Time
0.0
04-12 Lower Limit of Power Voltage Detect 150.0~210.0/300.0~420.0 190.0/380.0
04-13
DC Injection Brake Level (%)@start
0.0~150.0 50.0
04-14
DC Injection Brake Time
(Seconds) @start
0.0~25.5 0.5
04-15
DC Injection Brake Start
Frequency (Hz) @stopped
0.10~10.00 1.50
04-16
DC Injection Brake
Level(%)@Stopped
0.0~150.0 50.0
04-17
DC Injection Brake Time
(Seconds) @stopped
0.0~25.5 0.5
04-18 Braking transistor action level
200V : 320~400
380V : 550~800
200V : 380
380V : 690